Product photo
Modular UPS 1200KVA
Online Double Conversion · 3 Phase In / 3 Phase Out · high-power modular architecture.
Series: HQ-M
Rated capacity
1200 kVA
Power modules
60 kVA modules · scalable configuration
Efficiency
Up to 96% (double conversion) · up to 99% (ECO)
Power factor
Output PF = 1 · Input PF > 0.99
| Parameter | Value |
|---|---|
| Topology | Online double conversion |
| Rated capacity | 1200 kVA |
| Power module capacity | 60 kVA |
| Modular expansion | Scalable, N+X redundancy supported |
| Input wiring | 3 Phase + N + PE |
| Rated input voltage | 380/400/415 VAC (line-line) |
| Rated input frequency | 50/60 Hz |
| Input voltage range | Wide input range (configuration-dependent) |
| Input frequency range | 40–70 Hz |
| Input power factor | > 0.99 |
| THDi | < 3% (linear load) · < 5% (non-linear load) |
| Bypass rated voltage | 380/400/415 VAC |
| Bypass transfer | Automatic / manual maintenance bypass supported |
| Battery | Configurable battery string (project-based) |
| Battery voltage | DC bus (configuration-dependent) |
| Output rated voltage | 380/400/415 VAC (line-line) |
| Output rated frequency | 50/60 Hz |
| Output power factor | 1 |
| Voltage regulation | High-precision regulation (balanced/unbalanced load supported) |
| THDu | ≤ 2% (linear load) · ≤ 4% (non-linear load) |
| Crest factor | 3:1 |
| Overload capability | Designed for high overload tolerance (details by configuration) |
| Display | Color touch screen + LED indicators |
| Protection class | IP20 |
| Communication | RS232/RS485; optional: SNMP / dry contact |
| Operating temperature | 0–40°C |
| Humidity | 0–95% (non-condensing) |
| Noise | Project-dependent (site conditions) |
| Standard | IEC62040-1-1; IEC62040-2; IEC62040-3 |
| Minimum order | 60 |